SparkQuote NEC Calculators MCP server
Endpoint: https://sparkquote.ai/mcp · Authentication: No auth
Calculate wire sizes, voltage drop, conduit fill, and other electrical values using NEC references. The endpoint needs no credentials.
How do I authenticate?
Add the endpoint directly in your client. The catalog records no authentication requirement; no OAuth sign-in or API key is configured in this setup. The live server may change.
Authentication and connection guideConnection specification
- Remote endpoint
https://sparkquote.ai/mcp- Browser access
- Not yet measured
- Declared MCP transport
- Streamable HTTP
- Live-validated MCP transport
- Streamable HTTP — Observed by the latest catalog validation
- Declared authentication
- No authentication
- Detected authentication
- No authentication detected or retained from publisher evidence
- Protocol lifecycle
- Stateful MCP · 2025-11-25
- Category
- Reference
Product documentation · Official listing documentation · ChatGPT app directory listing
More Reference MCP servers · Browse all MCP servers · Test this endpoint in the MCP Playground
Connect it
Live-validated endpoint: https://sparkquote.ai/mcp · Streamable HTTP. No authentication is required by the catalog listing.
Agent prompt for Claude Code or Codex
Add the SparkQuote NEC Calculators MCP server to my MCP client configuration and verify that it works. What it is: Calculate wire sizes, voltage drop, conduit fill, and other electrical values using NEC references. The endpoint needs no credentials. Server URL: https://sparkquote.ai/mcp Transport: Streamable HTTP (remote MCP server, no local install). Authentication: none. The server accepts connections without credentials. Tools (10, as last observed by mcptest): bid_calculator, box_fill, conduit_fill, load_calculator, nec_ampacity, ohms_law, panel_schedule, voltage_drop, watts_to_amps, wire_size. Reference: https://mcptest.io/servers/sparkquote-nec-calculators/ Steps: 1. Work out which MCP client I use (Claude Code, Codex, Cursor, VS Code or another) and add the server under the name "sparkquote-nec-calculators" in that client's MCP configuration, user scope unless I ask otherwise. Claude Code: claude mcp add --transport http --scope user 'sparkquote-nec-calculators' 'https://sparkquote.ai/mcp' Codex: codex mcp add 'sparkquote-nec-calculators' --url 'https://sparkquote.ai/mcp' Other clients: use the setup for that client on the reference page. 2. Never write a credential value into a file that could be committed; reference an environment variable or the client's secret store, and ask me for any value you need. 3. Verify: connect to the server and call tools/list. Confirm the tools above are listed, and report any sign-in step I still have to complete.
Claude Code setup
Run in a terminal. This user-scoped entry is available across projects.
claude mcp add --transport http --scope user 'sparkquote-nec-calculators' 'https://sparkquote.ai/mcp'Codex CLI setup
Run in a terminal; Codex stores the entry in ~/.codex/config.toml.
codex mcp add 'sparkquote-nec-calculators' --url 'https://sparkquote.ai/mcp'Cursor setup
Add to .cursor/mcp.json for this project, or ~/.cursor/mcp.json for all projects.
{
"mcpServers": {
"sparkquote-nec-calculators": {
"url": "https://sparkquote.ai/mcp"
}
}
}VS Code setup
Add to .vscode/mcp.json, or run “MCP: Open User Configuration” for a private user-level entry.
{
"servers": {
"sparkquote-nec-calculators": {
"type": "http",
"url": "https://sparkquote.ai/mcp"
}
}
}Claude setup
Add the endpoint above in Claude:
- Customize > Connectors > Add custom connector
- Team/Enterprise: Organization settings > Connectors > Add > Custom > Web
Claude Desktop setup
Add the endpoint above in Claude Desktop:
- Remote: Customize > Connectors (same as claude.ai)
- Local: Settings > Developer > Edit Config, or Settings > Extensions for .mcpb files
~/Library/Application Support/Claude/claude_desktop_config.json(macOS) or%APPDATA%\Claude\claude_desktop_config.json(Windows), local servers only
ChatGPT setup
Add the endpoint above in ChatGPT:
- ChatGPT web: Plugins > Add custom MCP server, then configure authentication and accept the risk warning
Windsurf setup
Add the endpoint above in Windsurf:
~/.config/devin/mcp_config.json(%APPDATA%\devin\mcp_config.jsonon Windows),serverUrlorurl- Cascade panel > ... > MCPs > Open MCP config file
Gemini CLI setup
Add the endpoint above in Gemini CLI:
gemini mcp add --transport http <name> <url>~/.gemini/settings.json(user) or.gemini/settings.json(project),mcpServers
MCP SDK setup
Add the endpoint above in MCP SDK:
- Programmatic:
new Client(...).connect(new StreamableHTTPClientTransport(url))
Client compatibility
| Client | Status | Why |
|---|---|---|
| Claude Code | Supported | Claude Code supports Streamable HTTP servers and servers without authentication. |
| Codex | Partial | Codex's documentation does not state support for servers without authentication. |
| Cursor | Supported | Cursor supports Streamable HTTP servers and servers without authentication. |
| VS Code | Supported | VS Code supports Streamable HTTP servers and servers without authentication. |
| Claude | Supported | Claude supports Streamable HTTP servers and servers without authentication. |
| Claude Desktop | Supported | Claude Desktop supports Streamable HTTP servers and servers without authentication. |
| ChatGPT | Partial | Stateful routing needs operational care: ChatGPT can preserve MCP sessions, but the deployment must route a session consistently and retain its state. |
| Windsurf | Partial | Windsurf's documentation does not state support for servers without authentication. |
| Gemini CLI | Supported | Gemini CLI supports Streamable HTTP servers and servers without authentication. |
| MCP SDK | Supported | MCP SDK supports Streamable HTTP servers and servers without authentication. |
Computed from this server's validated transport, protocol and authentication against documented client support. Checks the catalog has not observed are not counted.
Latest validation evidence
- Validation status
- Online when last tested
- Validation checked at
- Nov 23, 2026 at 7:19 PM
- Validation detail
- Negotiated stateful MCP 2025-11-25 at https://sparkquote.ai/mcp; detected transport streamable-http; authentication none
Tool inventory
What the catalog validator observed on at https://sparkquote.ai/mcp without credentials. The live server may have changed since; connect in the Playground for the current list.
Tools provided by SparkQuote NEC Calculators 10
bid_calculatoroutputSchema declaredElectrical bid price from materials, markup, labor hours and rate, job costs, overhead and a target net margin (price = break-even / (1 − margin)).
Input
direct?: number, hours: number, margin: number, markup?: number, materials: number, overhead: number, rate: numberdirect?: numberoptionalPermits and other job costs ($). Optional.
hours: numberrequiredLabor hours (h).
margin: numberrequiredTarget net margin (%).
markup?: numberoptionalMaterial markup (%). Optional.
materials: numberrequiredMaterial cost ($).
overhead: numberrequiredOverhead (% of direct cost) (%).
rate: numberrequiredBurdened labor cost ($/h).
box_filloutputSchema declaredMinimum outlet box volume from NEC 314.16(B): conductor, device (2 each), clamp and grounding allowances times the Table 314.16(B) volume for the largest conductor.
Input
awg: string, boxVolume?: number, clamps: string, conductors: number, devices: number, grounds: number, supports?: numberawg: stringrequiredLargest conductor. "6" = 6 AWG; "8" = 8 AWG; "10" = 10 AWG; "12" = 12 AWG; "14" = 14 AWG; "16" = 16 AWG; "18" = 18 AWG.
boxVolume?: numberoptionalMarked box volume (blank for minimum only) (in³). Optional.
clamps: stringrequiredInternal cable clamps. "0" = None; "1" = One or more.
conductors: numberrequiredInsulated conductors (not counting grounds).
devices: numberrequiredDevices (switches, receptacles).
grounds: numberrequiredEquipment grounds entering box (count).
supports?: numberoptionalSupport fitting types (stud / hickey). Optional.
conduit_filloutputSchema declaredPercent fill and maximum number of THHN/THWN-2 conductors of one size in EMT or PVC Schedule 40, from NEC Chapter 9 Tables 1, 4 and 5.
Input
awg: string, count: number, groups?: string, size: string, type: stringawg: stringrequiredTHHN/THWN-2 size. "1" = 1 AWG; "2" = 2 AWG; "3" = 3 AWG; "4" = 4 AWG; "6" = 6 AWG; "8" = 8 AWG; "10" = 10 AWG; "12" = 12 AWG; "14" = 14 AWG; "1/0" = 1/0 AWG; "2/0" = 2/0 AWG; "3/0" = 3/0 AWG; "4/0" = 4/0 AWG.
count: numberrequiredNumber of conductors.
groups?: stringoptionalMixed THHN/THWN-2 groups: quantity, size per line (blank uses the single-size inputs)
size: stringrequiredTrade size. "1" = 1"; "2" = 2"; "3" = 3"; "4" = 4"; "1/2" = 1/2"; "3/4" = 3/4"; "1-1/4" = 1-1/4"; "1-1/2" = 1-1/2"; "2-1/2" = 2-1/2"; "3-1/2" = 3-1/2".
type: stringrequiredConduit type. "EMT" = EMT; "PVC-40" = PVC Schedule 40.
load_calculatoroutputSchema declaredDwelling service load by the NEC 220.82 optional method: 3 VA/ft² lighting, small-appliance and laundry circuits, fixed appliances, demand factor, heating or cooling, and the minimum standard service size. Leave an appliance out to count it as 0 VA.
Input
dishwasher?: number, disposal?: number, dryer?: number, ev?: number, heater?: number, hvac?: number, laundry: string, other?: number, range?: number, small: number, sqft: numberdishwasher?: numberoptionalDishwasher (VA). Optional.
disposal?: numberoptionalDisposal (VA). Optional.
dryer?: numberoptionalDryer (VA). Optional.
ev?: numberoptionalEV charger (VA). Optional.
heater?: numberoptionalWater heater (VA). Optional.
hvac?: numberoptionalLargest of heating or cooling (VA). Optional.
laundry: stringrequiredLaundry circuit. "1" = Yes (1,500 VA); "0" = No.
other?: numberoptionalOther fixed appliances (VA). Optional.
range?: numberoptionalRange / cooktop (VA). Optional.
small: numberrequiredSmall-appliance circuits.
sqft: numberrequiredLiving area (ft²).
nec_ampacityoutputSchema declaredAllowable ampacity of one insulated conductor from NEC Table 310.16 (not more than three current-carrying conductors in a raceway or cable, 30°C ambient), before any adjustment or correction factors and before the 240.4(D) small-conductor limits.
Input
material: string, size: string, temp: stringmaterial: stringrequired"cu" = copper; "al" = aluminum.
size: stringrequiredConductor size: AWG ("14" … "4/0") or kcmil ("250" … "500").
temp: stringrequiredTemperature column in °C: 60 (NM-B, UF), 75 (THWN, most terminations), 90 (THHN, for derating).
ohms_lawoutputSchema declaredOhm's law and power: give exactly two of voltage, current, resistance and power; the other two are calculated.
Input
i?: number, p?: number, r?: number, v?: numberi?: numberoptionalCurrent (A). Optional.
p?: numberoptionalPower (W). Optional.
r?: numberoptionalResistance (Ω). Optional.
v?: numberoptionalVoltage (V). Optional.
panel_scheduleoutputSchema declaredLays circuits out on a 120/240 V single-phase or 208Y/120 V three-phase panel and totals the load per phase with the imbalance.
Input
circuits: string, spaces: string, system: stringcircuits: stringrequiredCircuits: description, breaker A, poles, VA (one per line)
spaces: stringrequiredSpaces. "12" = 12; "20" = 20; "24" = 24; "30" = 30; "42" = 42.
system: stringrequiredPanel. "1" = 120/240 V single-phase; "3" = 208Y/120 V three-phase.
voltage_dropoutputSchema declaredVoltage drop for a given conductor size, current and one-way length, single- or three-phase, from NEC Chapter 9 Table 8 circular mils (VD = 2·K·I·L / CM, or √3 for three-phase).
Input
amps: number, awg: string, feet: number, material: string, phase: string, volts: stringamps: numberrequiredLoad current (A).
awg: stringrequiredSize. "14" = 14 AWG; "12" = 12 AWG; "10" = 10 AWG; "8" = 8 AWG; "6" = 6 AWG; "4" = 4 AWG; "3" = 3 AWG; "2" = 2 AWG; "1" = 1 AWG; "1/0" = 1/0 AWG; "2/0" = 2/0 AWG; "3/0" = 3/0 AWG; "4/0" = 4/0 AWG; "250" = 250 kcmil; "300" = 300 kcmil; "350" = 350 kcmil; "400" = 400 kcmil; "500" = 500 kcmil.
feet: numberrequiredOne-way distance (ft).
material: stringrequiredConductor. "cu" = Copper; "al" = Aluminum.
phase: stringrequiredPhase. "1" = Single-phase; "3" = Three-phase.
volts: stringrequiredVoltage. "120" = 120 V; "208" = 208 V; "240" = 240 V; "277" = 277 V; "480" = 480 V.
watts_to_ampsoutputSchema declaredCurrent drawn by a load in watts at a voltage and power factor, single- or three-phase, plus the 125% continuous-load value.
Input
pf: number, phase: string, volts: string, watts: numberpf: numberrequiredPower factor.
phase: stringrequiredPhase. "1" = Single-phase; "3" = Three-phase.
volts: stringrequiredVoltage. "120" = 120 V; "208" = 208 V; "240" = 240 V; "277" = 277 V; "480" = 480 V.
watts: numberrequiredPower (W).
wire_sizeoutputSchema declaredMinimum conductor size for a circuit: NEC Table 310.16 ampacity at the termination temperature rating, the 240.4(D) small-conductor limits, voltage drop over the run, and the Table 250.122 equipment grounding conductor, increased in proportion under 250.122(B) when voltage drop upsizes the conductors.
Input
amps: number, feet: number, limit: number, material: string, phase: string, temp: string, volts: stringamps: numberrequiredBreaker / load (A).
feet: numberrequiredOne-way distance (ft).
limit: numberrequiredMax voltage drop (%).
material: stringrequiredConductor. "cu" = Copper; "al" = Aluminum.
phase: stringrequiredPhase. "1" = Single-phase; "3" = Three-phase.
temp: stringrequiredTermination rating. "60" = 60°C (NM-B, UF); "75" = 75°C (THHN in conduit); "90" = 90°C.
volts: stringrequiredVoltage. "120" = 120 V; "208" = 208 V; "240" = 240 V; "277" = 277 V; "480" = 480 V.